The SS-XP6C is a 6 Circuit Supervised Control Output Module for use with the FireSense 2800 & 3030 Series Intelligent alarm system. Each module is intended for switching applications involving AC or DC, which require wiring supervision.
A common loop input is used for all modules. Each module has its own address. A pair of rotary code switches is used to set the address of the first module. The remaining modules are automatically assigned to the next five higher addresses. Provisions are included for disabling a maximum of three unused modules to release the addresses to be used elsewhere (you will need to power cycle the module for this to take effect).
Each module has terminals for connection to an external supply circuit for powering ancillary devices. Jumpers are also provided to common up the power supply to all 6 modules.